CHAPTER 2 CONNECTING POWER AND SURGE PROTECTION 19
Sensor
Pole
Mount
Trac
Cabinet
Main Trac Cabinet
Both ends of the home-
run cable connect to the
UNPROTECTED side of the
surge modules
Figure 2.2 – Typical Cable Run
e Click 200 contains three terminal connectors on both the top and the bottom of the
module (see Figure 2.3). e terminal connectors are removable and are red-keyed, allow-
ing the connector to plug into only one specic jack. is both simplies the wiring process
and reduces the possibility of wiring errors.
e back four terminals consist of one +DC power, -DC and two surge ground connec-
tions; the middle four terminals are for RS-485 communication and consist of a +485 con-
nection, a -485 connection, an RS-232 ground connection and a surge ground connection;
the front four terminals are for RS-232 communication and consist of TD, RD, CTS and
RTS.