CHAPTER 5  SETTINGS 49
Green highlight – is indicates the communication link (port) on which SSMHD is
connected.
RS-485 – Allows you to set the baud rate for RS-485 communication. e Response
Delay setting is used to congure how long the sensor will wait before responding to
a message received. is is useful for some communications devices that are unable to
quickly change transmission direction. e default value is 10 milliseconds.
e Termination checkbox allows you to electronically turn RS-485 communication
bus termination on or o. Only the end devices on a RS-485 bus should be terminated.
In general, the termination can be le unchecked until a multi-drop bus becomes over-
loaded.
RS-232 – Allows you to set the baud rate for RS-232 communication. e Response
Delay setting works the same as the RS-485 section.
e HW Handshaking checkbox should be selected if you are connecting your sensor to
an RS-232 device (such as some modems). ese devices sometimes require ow control
handshaking because they cannot keep up with the data rates of higher-performance
devices like personal computers and SmartSensor HD. SmartSensor Manager HD and
SmartSensor HD have built-in support for RS-232 ow control hardware handshaking;
this support allows the SmartSensor HD and SmartSensor Manager HD to work with
these slower modem connections. Table 5.1 gives a brief description of each RS-232 line.
Line Description
TX Transmit data line
RX Data receive line
RTS Request to send flow control hardware handshaking line
CTS Clear to send flow control hardware handshaking line
Table 5.1 – RS-232 Lines
In order to use hardware handshaking, the sensor’s RTS and CTS signals must be properly
connected. If the Flow Control option under the Serial connection screen is set to Hard-
ware, you will not be able to connect if the sensor’s HW handshaking setting has been
previously turned o. e reason you cannot connect is that the sensors RTS line is not
asserted; as that line is connected to the computer’s CTS line, the computer will not forward
data messages it is given by SmartSensor Manager HD. To successfully connect, simply
change the Flow Control setting to None.
Outputs Tab
e Outputs tab contains the following settings (see Figure 5.4):